Single-phase power regulator G3PW

Single-phase power regulator G3PW

The power controller improves functionality and performance. A single phase power controller that provides high precision and multiple functions.
[Features]
· Uses heat resistance values to sense heater burnout, enabling even more accurate burnout detection. Can detect a single burnout among multiple heaters.
· The digital display allows you to monitor set values, output levels and operation times.
· The control mode can be selected (phase control or optimum cycle control).
· RS-485 communications to set output variables and monitor the load current.
· Features 4 output modes for phase control: proportional to phase angle, proportional to voltage, proportional to square voltage, and constant-current control.
· Compatible with a wide variety of loads (transformer loads, alloy heaters, pure metal heaters, etc.) UL and CE marking compliant.
[Applications]
· Switching element for power control. Unlike transistors, this can be operated with an AC power supply.

Edit Part Configuration

Part Number

Configured Part Number is shown.

Part Number
G3PW-A220EC-C-FLK
G3PW-A220EU-C
G3PW-A220EU-S
G3PW-A245EC-C-FLK
G3PW-A245EU-C
G3PW-A245EU-S
G3PW-A260EC-C-FLK
G3PW-A260EU-C
G3PW-A260EU-S
G32X-V2K
Part NumberVolume DiscountDays to Ship Type Terminal block type MAX rated current
(A)
Current control Notes

4 Days or more

Main bodyScrewless clamp20Constant current typeIncludes heater open-circuit detection/RS-485 communication

5 Days or more

Main bodyScrewless clamp20Standard type (without constant current control)-

5 Days or more

Main bodySmall slotted screw20Standard type (without constant current control)-

5 Days or more

Main bodyScrewless clamp45Constant current typeIncludes heater open-circuit detection/RS-485 communication

5 Days or more

Main bodyScrewless clamp45Standard type (without constant current control)-

5 Days or more

Main bodySmall slotted screw45Standard type (without constant current control)-

5 Days or more

Main bodyScrewless clamp60Constant current typeIncludes heater open-circuit detection/RS-485 communication

5 Days or more

Main bodyScrewless clamp60Standard type (without constant current control)-

5 Days or more

Main bodySmall slotted screw60Standard type (without constant current control)-

4 Days or more

External setting volume---Resistance value: 2 Ω